What size UPS do I need? Sizing capacity and runtime

My equipment adds up to 2000 W, so is a 2000 VA UPS enough? That calculation almost always ends in the wrong purchase. What is missing is not addition — it is three correction factors.

Step 1: count the real load, not the nameplate load

List the protected equipment one by one, with the power on its nameplate (in W or VA). Two rules:

  • Count critical equipment only. Printers, water coolers and photocopiers should not be on a UPS — their heating elements draw a large amount of power in an instant.
  • Convert VA to W. If a device is rated only in VA, multiply by the power factor (for computer-type loads, roughly 0.7–0.9) to get W.

Step 2: deal with start-up inrush

This is where sizing most often comes unstuck. The current drawn at the instant a motor, compressor, transformer or large-capacitance device starts can be 3–7 times its rated value.

There are three ways to handle it: size the UPS for the inrush; choose an online model with high overload capacity for those loads; or, for motors, move to a variable-speed drive or add a soft starter. If your list includes air conditioning, water pumps, pick-and-place machines or large photocopiers, this step cannot be skipped.

Step 3: leave headroom

Take the result of the first two steps and multiply by a headroom factor of 1.3–1.5, to cover:

  • equipment added in future
  • reduced output as the batteries age
  • avoiding the overheating that comes from running at full load for long periods

Step 4: decide the runtime

Ask yourself one question: once the mains fails, what do I want to happen?

Requirement Suggested runtime
Just avoid the equipment restarting 5–10 minutes
Complete a safe shutdown 10–20 minutes
Hold on until a generator takes over 15–30 minutes
Ride out a whole unplanned outage 1 hour or more

Runtime rises in proportion to battery count, and so does cost. Protecting only what genuinely needs it is often cheaper than buying a larger unit.

The three most common mistakes

  1. Adding up nameplate wattage and ignoring start-up inrush — the unit alarms on overload as soon as it is switched on.
  2. Treating VA as usable power — the unit you buy cannot carry the load you expected.
  3. Oversizing "for safety" — more money, more space, and a battery that sits in shallow discharge with poorer efficiency.

The most reliable approach is still a site survey. Send us your load list and a photo of the installation, and an engineer will size it against the real conditions and explain the basis for every number. You can browse the UPS range first, or contact us.

Frequently asked questions

The listing says 1000 VA / 600 W — which number do I use?
Use the W figure. W is the real power the UPS can actually deliver, while VA is apparent power including the reactive component. Compare W against your real load, or you will end up with a unit whose label looks generous but which cannot carry the load.
How much battery do I need for one hour?
A rough estimate is battery capacity (Ah) × string voltage (V) × 0.8 (efficiency and discharge factor) ÷ load (W) = hours. For example, 100 Ah × 48 V × 0.8 ÷ 1000 W ≈ 3.8 hours. The real figure depends on discharge rate, temperature and battery ageing, so check the manufacturer's discharge curve.
Why is headroom so important?
It absorbs start-up inrush and future expansion, and it keeps the UPS from running at over 90% load for long periods, which generates heat and shortens life. In practice, aim for a load between 40% and 70% of rated capacity.