LEOCH DJ series 12 V AGM batteries
The battery type small equipment uses most. Compact and maintenance-free — but there is one rule that has to hold when you replace them.
Product photo
- Brand
- LEOCH
- Type
- Valve-regulated lead-acid (AGM)
- Typical use
- Small UPS, access control, CCTV, emergency lighting
- Models covered
- LEOCH DJ series (12 V, 1.2–28 Ah by capacity)
- Category
- Batteries and battery packs / VRLA / AGM batteries
The shared weakness of this class: treated as a part that needs no attention
The problem with small batteries is not quality — it is being ignored.
The UPS gets installed, recorded and looked at. The batteries sit deep inside a cabinet or inside a device, and nobody finds out they have failed until the day the power goes — and usually at the worst possible moment.
What we recommend: an actual discharge test once a year, not a voltage reading, with the measured runtime recorded. Once it has fallen more than 30% below the original figure, schedule a full string replacement. That costs far less than discovering the failure during an outage.
How we handle replacement
- Test before replacing — we measure the real discharge capability of the existing string on site, to confirm replacement is genuinely needed and the issue is not a UPS setting or the load.
- Whole string, same batch — no mixing old and new, so the string stays consistent.
- Equivalent specification — we do not casually change capacity or dimensions, so it fits and it charges properly.
- Old battery collection — lead-acid is controlled waste; we take it away rather than leaving it with you.
- A test record on handover — we measure runtime after replacement and confirm it is back where it should be.
The battery is the only part of a UPS system that wears out. It deserves a line in the maintenance budget, and it is worth doing properly.
Key features
- Valve-regulated (VRLA) construction: no topping up, no acid mist
- Can be installed in any orientation except inverted, so it fits inside small equipment
- Low self-discharge, suited to standby duty
- For small UPS, access control, CCTV and emergency lighting
- Stable supply — common capacities are held in stock
Where it fits
Small UPS and standby power
The standard battery size for domestic and small UPS units, with a predictable replacement cycle.
Access control and CCTV
Keeps door controllers and cameras running through an outage.
Emergency lighting and alarms
Low self-discharge suits long periods on standby.
Frequently asked questions
Can I replace just one block?
How do I know the batteries need replacing?
Why do they not last as long as the label says?
Related models & accessories
LEOCH DJW series
A general-purpose 12 V battery, and one of the most common specifications inside a cabinet UPS string.
View detailsCSB GP series
A standard battery specification for small UPS and security equipment. When replacing them, the thing that matters is not the brand — it is replacing the whole string.
View detailsSPRM1KL battery pack
The original battery pack for a rack-mount UPS — replacing the whole pack is more reliable than assembling it block by block, and it lasts longer.
View detailsSpecifications
| Voltage | 12 V (per block) |
|---|---|
| Capacity range | Around 1.2–28 Ah (by model) |
| Type | Valve-regulated lead-acid (AGM) |
| Design life | 3–5 years on float, depending on conditions |
| Maintenance | No topping up; check terminal voltage and appearance annually |
| Mounting | Any orientation except inverted |
| Typical equipment | Small UPS, access control, CCTV, emergency lighting, instruments |
Specifications follow the manufacturer's latest data. Actual configuration must be sized against the site load, required runtime and distribution environment — this table is for selection reference only.